The Tripp Lite SMX1500XLRT2U is a 1500VA/1000W line-interactive UPS system offering robust power protection for servers networking equipment and other sensitive electronics. Its 2U rack/tower convertible design allows for flexible installation in various IT environments. This international model features a 230V input.
With automatic voltage regulation (AVR) the SMX1500XLRT2U corrects minor voltage fluctuations without switching to battery power extending battery life. It provides ample runtime to allow for safe system shutdowns during outages ensuring data integrity and minimizing downtime.
| APPLICATIONS | |
| UPS Applications | Large Network; High-End Desktop/Small Network |
| COMMUNICATIONS | |
| Communications Cable | USB and DB9 cabling included |
| Communications Interface | Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
| Emergency Power Off (EPO)/Remote On-Off (ROO) | Yes |
| Network Management Card Description | One slot for optional WEBCARDLXE web card. Note: Not compatible with WEBCARDLX |
| Network Monitoring Port Description | Network Card Optional. Not compatible with WEBCARDLX. |
| Network UPS Tools (NUT) Compatibility | NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite |
| PowerAlert Software | For local monitoring via the UPSs built-in communication ports download PowerAlert Office software at https://tripplite.eaton.com/poweralert |
| DETAIILS | |
| Manufacturer | Tripp Lite |
| Manufacturer Part Number | SMX1500XLRT2U |
| FEATURES & SPECIFICATIONS | |
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported |
| Green Energy-Saving Features | Greater than 95% efficiency - GREEN UPS; Individually controllable load banks |
| Grounding Details | Rear panel grounding lug |
| High Availability UPS Features | Hot swappable batteries; Surge/noise protection |
| LINE / BATTERY TRANSFER | |
| High Voltage Transfer to Battery Power (Setpoint) | 294V (Normal/Extended Modes) |
| Low Voltage Transfer to Battery Power (Setpoint) | 160V (Normal mode) 150V (Extended Mode) |
| Transfer Time | 1-4ms for normal mode >5ms for sensitive mode |
| OVERVIEW | |
| UPC Code | 037332119216 |
| UPS Type | Line-Interactive |
| STANDARDS & COMPLIANCE | |
| Product Certifications | CAN/CSA C22.2; EN 62040-2; EN 62040-3; ICES (Canada); IEC 62040-2; NOM (Mexico); UL 1778; cTUVus |
| Product Compliance | CE (Europe); ENERGY STAR Qualified; FCC (USA); FCC Part 15 Class A (USA); RoHS3; UKCA; WEEE |
| SURGE / NOISE SUPPRESSION | |
| AC Suppression Joule Rating | 175 |
| AC Suppression Response Time | Instantaneous |
| EMI / RFI AC Noise Suppression | Yes |
| USER INTERFACE ALERTS & CONTROLS | |
| Alarm Cancel Operation | Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
| Audible Alarm | Audible alarm indicates UPS startup power-failure low-battery overload UPS fault and remote shutdown conditions |
| Front Panel LCD Display | Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data plus configuration of voltage operating mode alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
| Switches | 5 pushbutton switches control OFF / ON power status ENTER UP and DOWN selection and ESC control functions |
| VOLTAGE REGULATION | |
| Overvoltage Correction | Reduces incoming voltage between 265-294V (Normal Mode / Extended Mode) by 13% |
| Severe Undervoltage Correction | UPS: 3 status-indicating LEDs (normal battery mode alarm/fault); LED colors (green = ON orange = On battery flashing orange = below warning level red = alarm/fault). |
| Undervoltage Correction | Increases incoming voltage between 162-184V (Normal Mode) or 151-184V (Extended Mode) by 15% |
| Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 150 to 294 |
| Battery | |
| Battery Access | Front panel battery access door |
| Battery Recharge Rate (Included Batteries) | Less than 4.5 hours from 10% to 90% (typical full load discharge) |
| Battery Replacement Description | Hot-swappable user replaceable batteries |
| DC System Voltage (VDC) | 48 |
| Expandable Runtime | Yes |
| Runtime Full Load (min.) | 5 min. (1500W) |
| Runtime Half Load (min.) | 14 min. (750W) |
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Details | |
| Category | UPS System |
| Environmental | |
| AC Mode BTU / Hr. (Full Load) | 106 |
| AC Mode Efficiency Rating (100% Load) | 98% |
| Audible Noise | 45 dBA maximum front side 1m |
| Battery Mode Heat Dissipation (BTU/Hr) @ Full Load | 699 |
| Operating Temperature Range | 32 to 104F (0 to 40C) |
| Relative Humidity | 20 to 95% non-condensing |
| Storage Elevation (ft.) | 0-32808 |
| Storage Elevation (m) | 0-10000 |
| Storage Temperature Range | 5 to 122F (-15 to 50C) |
| Operating Elevation | 0-10000 ft. (0-3000 m) |
| Input | |
| Input Phase | Single-Phase |
| Maximum Input Amps | 10 |
| Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
| Rated input current (Maximum Load) | 10A |
| UPS Input Connection Description | IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
| UPS Input Connection Type | C14 inlet |
| Output | |
| Frequency Compatibility | 50 / 60 Hz |
| Frequency Compatibility Details | Automatic frequency selection |
| Hot-Swap PDU options | PDUBHV10 (2U / 8 C13 outlets) |
| Included Output Power Cables | Set of 2 C13 to C14 power cables included |
| Individually Controllable Load Banks | Yes |
| Load Management Receptacles | Two switchable two-outlet C13 load banks |
| Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V |
| Nominal Voltage Details | 208V nominal output in battery mode |
| Output AC Waveform (AC Mode) | Pure Sine wave |
| Output AC Waveform (Battery Mode) | Pure Sine wave |
| Output Capacity (kVA) | 1.5 |
| Output Capacity (kW) | 1.5 |
| Output Capacity (VA) | 1500 |
| Output Capacity (Watts) | 1500 |
| Output Receptacles | (8) C13 |
| Output Voltage Regulation (Battery Mode) | -10% +6% |
| Output Voltage Regulation (Line Mode) | 208V (-13% +15%) |
| Power Factor | 1.0 |
| Physical | |
| Cooling Method | Fan |
| Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount; Tower |
| Minimum Required Rack Depth (cm) | 53.34 |
| Minimum Required Rack Depth (inches) | 21 |
| Minimum Required Rack Depth with External Battery Pack (cm) | 53 |
| Minimum Required Rack Depth with External Battery Pack (in.) | 21 |
| Minimum Required Rack Depth without External Battery Pack (cm) | 53 |
| Minimum Required Rack Depth without External Battery Pack (in.) | 21 |
| Mounting Details | Included 4-post mounting kit enables installation in 4 post racks. Two ABS mounting stands enables the UPS to be configured in an upright tower orientation. |
| Primary Form Factor | Rackmount |
| Primary UPS Depth (mm) | 447 |
| Primary UPS Height (mm) | 86 |
| Primary UPS Width (mm) | 437 |
| Shipping Dimensions (hwd / cm) | 23.88 x 49.78 x 58.42 |
| Shipping Dimensions (hwd / in.) | 9.40 x 19.60 x 23.00 |
| Unit Dimensions (hwd / in.) | 3.400 x 17.200 x 17.600 |
| Unit Weight (kg) | 22.41 |
| Unit Weight (lbs.) | 49.4 |
| UPS Housing Material | Steel |
| UPS Power Module Dimensions (hwd cm) | 8.64 x 43.69 x 44.70 |
| UPS Power Module Dimensions (hwd in.) | 3.4 x 17.2 x 17.6 |
| UPS Power Module Weight (kg) | 22.41 |
| UPS Power Module Weight (lbs.) | 49.4 |
| Rack Height | 2U |
| Shipping Weight (kg) | 27.90 |
| Shipping Weight (lbs.) | 61.50 |
| Warranty | |