Tripp Lite SMART2200RM2U SmartPro 1950VA 1950W 120V Line-Interactive Sine Wave UPS - 7 Outlets Network Card Option LCD USB DB9 2U Rack/Tower UPS Battery Backup

Tripp Lite SMART2200RM2U SmartPro 1950VA 1950W 120V Line-Interactive Sine Wave UPS - 7 Outlets Network Card Option LCD USB DB9 2U Rack/Tower

$1,135.00
Manufacturer:Eaton / Tripp Lite
Model:SMART2200RM2U
Condition:New
Availability:In Stock
Datasheet

The Tripp Lite SMART2200RM2U 2200VA/1920W UPS provides robust power protection for critical IT equipment. Featuring automatic voltage regulation (AVR) it corrects brownouts and overvoltages without using battery power extending battery life. It's ideal for rackmount servers networking devices and other sensitive electronics.

With USB and DB9 connectivity this 2U rackmount UPS enables convenient monitoring and control. Its LCD interface provides real-time power status information. Protect your valuable equipment from outages and surges with the Tripp Lite SMART2200RM2U.

APPLICATIONS
UPS Applications High-End Desktop/Small Network; Large Network
COMMUNICATIONS
Communications Cable USB and DB9 cabling included
Communications Interface Contact closure; DB9 Serial; Slot for SNMP/Web interface; USB (HID enabled)
Emergency Power Off (EPO)/Remote On-Off (ROO) Yes
Network Management Card Description One slot for optional WEBCARDLXE web card. Note: Not compatible with WEBCARDLX
Network Monitoring Port Description Network Card Optional. Not compatible with WEBCARDLX
Network UPS Tools (NUT) Compatibility NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite
PowerAlert Software For local monitoring via the UPSs built-in communication ports download PowerAlert Office software at https://www.tripplite.com/poweralert
DETAIILS
Manufacturer Tripp Lite
Manufacturer Part Number SMART2200RM2U
FEATURES & SPECIFICATIONS
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
Green Energy-Saving Features Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Grounding Details Rear panel grounding lug
High Availability UPS Features Automatic Voltage Regulation (AVR); Hot swappable batteries; Remote management; Sine wave output; Surge/noise protection
LINE / BATTERY TRANSFER
High Voltage Transfer to Battery Power (Setpoint) 151
Low Voltage Transfer to Battery Power (Setpoint) 80
Transfer Time 1-4ms for normal mode
OVERVIEW
UPC Code 037332150622
UPS Type Line-Interactive
STANDARDS & COMPLIANCE
Product Certifications CSA (Canada); UL 1778; NOM (Mexico)
Product Compliance ENERGY STAR Qualified; FCC Part 15 Class A (USA); RoHS
SURGE / NOISE SUPPRESSION
AC Suppression Joule Rating 380
AC Suppression Response Time Instantaneous
EMI / RFI AC Noise Suppression Yes
USER INTERFACE ALERTS & CONTROLS
Alarm Cancel Operation Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes the alarm beeps again overriding the previous alarm silencing
Audible Alarm Audible alarm indicates UPS startup power-failure low-battery overload UPS fault and remote shutdown conditions
Front Panel LCD Display Front panel rotatable LCD information and configuration screen offers detailed UPS and site power status and operating data plus configuration of voltage operating mode alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
LED Indicators 3 status-indicating LEDs (normal battery mode alarm); LED light bar (blue = nominal blinking blue = warning red = alarm)
Switches 5 pushbutton switches control OFF / ON power status ENTER UP and DOWN selection and ESC control functions
VOLTAGE REGULATION
Overvoltage Correction Reduces incoming voltage between 132-151V by 13% (Normal Mode); 138-152V (Extended mode)
Undervoltage Correction Boost incoming voltages between 81-102V by 15% (Normal Mode); 71-92V by 15% (Extended Mode)
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 81 to 150V (Normal mode) adjustable to 70-153V (Extended mode)
Battery
Battery Access Front panel battery access door
Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90% (typical full load discharge)
Battery Replacement Description Hot-swappable user replaceable batteries
DC System Voltage (VDC) 72
Expandable Runtime No
Runtime Full Load (min.) 4 min. (1950W)
Runtime Half Load (min.) 12 min. (975W)
Battery Type Valve Regulated Lead Acid (VRLA)
Details
Category UPS System
Environmental
AC Mode BTU / Hr. (Full Load) 109
AC Mode Efficiency Rating (100% Load) 96%
Audible Noise 45 dBA maximum front side 1m
Battery Mode Heat Dissipation (BTU/Hr) @ Full Load 591
Operating Temperature Range 32 to 104F (0 to 40C)
Relative Humidity 20 to 95% non-condensing
Storage Elevation (ft.) 0-32808
Storage Elevation (m) 0-10000
Storage Temperature Range 5 to 122F (-15 to 50C)
Operating Elevation 0-10000 ft. (0-3000 m)
Input
Input Phase Single-Phase
Maximum Input Amps 16
Nominal Input Voltage Description 80V-151V; adjustable to 70-153V
Nominal Input Voltage(s) Supported 120V AC
Rated input current (Maximum Load) 16A (120V)
Recommended Electrical Service 20A 120V
UPS Input Connection Type 5-20P
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3.1
Output
Frequency Compatibility 50 / 60 Hz
Individually Controllable Load Banks Yes
Load Management Receptacles Two switched single outlet load banks (2x 5-20R and 2x 5-20R)
Nominal Output Voltage(s) Supported 100V; 110V; 120V; 125V
Nominal Voltage Details 120v nominal output in battery mode
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
Output Capacity (kVA) 1.95
Output Capacity (kW) 1.95
Output Capacity (VA) 1950
Output Capacity (Watts) 1950
Output Receptacles (6) 5-20R; (1) L5-20R
Output Voltage Regulation (Battery Mode) -10% +6%
Output Voltage Regulation (Line Mode) 120V (-13% +15%)
Power Factor 1.0
Physical
Cooling Method Fan
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount; Tower
Minimum Required Rack Depth (cm) 68.58
Minimum Required Rack Depth (inches) 27
Mounting Details Included mounting bracket enables installation in 4 post racks. Two ABS mounting stands enables the UPS to be configured in an upright tower orientation.
Primary Form Factor Rackmount; Tower
Primary UPS Depth (mm) 602
Primary UPS Height (mm) 86
Primary UPS Width (mm) 437
Shipping Dimensions (hwd / cm) 23.88 x 57.91 x 78.49
Shipping Dimensions (hwd / in.) 9.40 x 22.80 x 30.90
Unit Dimensions (hwd / in.) 3.400 x 17.000 x 23.700
Unit Weight (kg) 29.62
Unit Weight (lbs.) 65.3
UPS Housing Material Steel
UPS Power Module Dimensions (hwd cm) 8.64 x 43.69 x 60.20
UPS Power Module Dimensions (hwd in.) 3.4 x 17.2 x 23.7
UPS Power Module Weight (kg) 35.65
UPS Power Module Weight (lbs.) 78.6
Rack Height 2U
Shipping Weight (kg) 35.61
Shipping Weight (lbs.) 78.50
Warranty
Warranty/Returns 30 Days