Tripp Lite PDUMNH20AT1 1.92kW 120V Single-Phase ATS/Monitored PDU - 16 5-15/20R Outlets Dual L5-20P/5-20P Inputs 12 ft. Cords 1U TAA PDU Series

Tripp Lite PDUMNH20AT1 1.92kW 120V Single-Phase ATS/Monitored PDU - 16 5-15/20R Outlets Dual L5-20P/5-20P Inputs 12 ft. Cords 1U TAA

$647.95
Manufacturer:Eaton / Tripp Lite
Model:PDUMNH20AT1
Condition:New
Availability:In Stock
The Tripp Lite PDUMNH20AT1 ATS/Monitored PDU provides 1.92kW and 20A via 16 5-15/20R outlets. Dual L5-20P inputs offer automatic switching for redundant power in 1U of rack space.
Datasheet

The Tripp Lite PDUMNH20AT1 ATS/Monitored PDU safeguards critical equipment with automatic transfer switching between two input power sources. This 1U rack-mountable unit distributes 1.92kW of power at 20A through 16 NEMA 5-15/20R outlets ideal for high-density applications.

Featuring dual L5-20P input plugs the PDUMNH20AT1 ensures continuous uptime by seamlessly switching to the secondary power source in the event of primary power failure. This makes it a reliable solution for servers network devices and other sensitive electronics in data centers and network closets.

COMMUNICATIONS
Communications Cable Micro-USB- to-USB A configuration/console Access cable
PowerAlert Software LX Platform Interface: PowerAlert Device Manager
DETAIILS
Manufacturer Tripp Lite
Manufacturer Part Number PDUMNH20AT1
FEATURES & SPECIFICATIONS
Grounding Rear grounding lug
High Availability PDU Features Auto-Transfer Switching
OVERVIEW
PDU Type Auto-Transfer Switch; Monitored
UPC Code 037332267153
STANDARDS & COMPLIANCE
Product Certifications RETIE (Colombia); CSA (Canada); NOM (Mexico); UL 62368-1
Product Compliance RoHS; FCC Part 15 Class A (USA); Trade Agreements Act (TAA)
SURGE / NOISE SUPPRESSION
Automatic Shut-Off No
USER INTERFACE ALERTS & CONTROLS
Front Panel LCD Display Digital display reports total PDU output current in amps
LED Indicators Primary and Secondary source selection status LEDs indicate which AC source is being supplied to the output of the ATS PDU
Details
Category Power Distribution Units (PDUs)
Environmental
Operating Temperature Range 32 to 104F (0 to 40C)
Relative Humidity 5% to 95% non-condensing
Storage Temperature Range -22 to 122F (-30 to 50C)
Operating Elevation 0-10000 ft. (0-3000 m)
Input
Input Connection Type Primary: Attached L5-20P Secondary: C20 inlet with detachable C19-to-L5-20P cordset; L5-20-to-L5-20P adapters
Input Cord Details Set of two L5-20P cordsets with two 5-20P adapters enable connection to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 12
Input Cord Length (m) 3.66
Input Phase Single-Phase
Maximum Input Amps 16
Maximum Input Amps Details Agency de-rated to 16A maximum
PDU Input Voltage 100; 120; 127
PDU Plug Type (2) NEMA 5-20P; (2) NEMA L5-20P
Recommended Electrical Service 20A 120V
Output
Frequency Compatibility 50 / 60 Hz
Output Capacity Details 2.03kW (127V) 1.92kW (120V) 1.6kW (100V) / 20A total capacity (Agency de-rated to 16A); 16A max per outlet
Output Nominal Voltage 100; 120; 127
Output Receptacles (16) 5-15/20R
Physical
Minimum Required Rack Depth (cm) 49.53
Minimum Required Rack Depth (inches) 19.5
PDU Form Factor Horizontal (1U)
Shipping Dimensions (hwd / in.) 5.40 x 23.30 x 20.10
Unit Dimensions (hwd / cm) 4.44 x 44.4 x 36.8
Unit Dimensions (hwd / in.) 1.750 x 17.500 x 14.500
Unit Weight (kg) 5.53
Unit Weight (lbs.) 12.2
Form Factors Supported 1U rackmount
Material Of Construction Metal
Rack Height 1U
Shipping Weight (kg) 9.39
Warranty