Tripp Lite PDUMH30HV 5.5kW Single-Phase Local Metered PDU 208/230V Outlets (16 C13 & 2 C19) L6-30P 12 ft. (3.66 m) Cord 2U Rack-Mount TAA PDU Series

Tripp Lite PDUMH30HV 5.5kW Single-Phase Local Metered PDU 208/230V Outlets (16 C13 & 2 C19) L6-30P 12 ft. (3.66 m) Cord 2U Rack-Mount TAA

$396.76
Manufacturer:Eaton / Tripp Lite
Model:PDUMH30HV
Condition:New
Availability:In Stock
The Tripp Lite PDUMH30HV Metered PDU distributes 208/240V 30A power to 16 C13 and 2 C19 outlets. Ideal for high-density rackmount applications with its horizontal 2U design.
Datasheet

The Tripp Lite PDUMH30HV Metered PDU provides reliable power distribution in demanding IT environments. Distributing 208V/240V at 30A this unit offers 16 C13 and 2 C19 outlets accommodating a variety of devices. Its horizontal 2U form factor makes it ideal for rackmount installations.

Featuring comprehensive metering capabilities the PDUMH30HV allows for accurate monitoring of power consumption. This helps optimize energy efficiency and prevent overloads. The robust L6-30P input ensures a secure connection to your power source making it a dependable solution for critical equipment.

DETAIILS
Manufacturer Tripp Lite
Manufacturer Part Number PDUMH30HV
FEATURES & SPECIFICATIONS
Grounding Grounding lug
OVERVIEW
PDU Type Local Metered
UPC Code 037332159021
STANDARDS & COMPLIANCE
Product Certifications NOM (Mexico); UL 62368-1
Product Compliance RoHS; FCC Part 15 Class A (USA); UKCA; Trade Agreements Act (TAA)
SURGE / NOISE SUPPRESSION
Automatic Shut-Off No
USER INTERFACE ALERTS & CONTROLS
Front Panel LCD Display Set of 2 digital meters continuously report output current for breakered load banks 1 & 2 (Bank 1: upper row of 9 outlets / Bank 2: lower row of 9 outlets)
Details
Category Power Distribution Units (PDUs)
Environmental
Operating Temperature Range 32 to 104F (0 to 40C)
Relative Humidity 5% to 95% non-condensing
Storage Temperature Range -22 to 122F (-30 to 50C)
Operating Elevation 0-10000 ft. (0-3000 m)
Input
Input Cord Length (ft.) 12
Input Cord Length (m) 3.66
Input Phase Single-Phase
Maximum Input Amps 24
Maximum Input Amps Details Agency de-rated to 24A continuous
PDU Input Voltage 208; 230
PDU Plug Type NEMA L6-30P
Recommended Electrical Service Single-phase 30A 208/230V service
Output
Frequency Compatibility 50 / 60 Hz
Output Capacity Details 5.5kW (230V) 5kW (208V) total capacity / 30A max (Agency de-rated to 24A) 20A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
Output Nominal Voltage 208/230V
Output Receptacles (16) C13; (2) C19
Overload Protection Two 20A breakers protect 9 outlets each
Physical
Minimum Required Rack Depth (cm) 40.64
Minimum Required Rack Depth (inches) 16
PDU Form Factor Horizontal (2U)
Shipping Dimensions (hwd / cm) 19.81 x 42.42 x 50.29
Shipping Dimensions (hwd / in.) 7.80 x 16.70 x 19.80
Unit Dimensions (hwd / cm) 8.8 x 44.4 x 31.8
Unit Dimensions (hwd / in.) 3.500 x 17.500 x 12.500
Unit Weight (kg) 6.21
Unit Weight (lbs.) 13.7
Form Factors Supported 2U rackmount; mounting accessories included
Material Of Construction Metal
Rack Height 2U
Shipping Weight (kg) 7.17
Shipping Weight (lbs.) 15.80
Warranty
Warranty/Returns 30 Days