Tripp Lite PDUH20DV 1.6-3.8kW Single-Phase 100-240V Basic PDU 14 Outlets (12 C13 & 2 C19) C20 with L6-20P Adapter 12 ft. (3.66 m) Cord 1U Rack-Mount
$158.47
Manufacturer:Eaton / Tripp Lite
Model:PDUH20DV
Condition:New
Availability:Out Of Stock
Condition:New
Availability:Out Of Stock
- Power Protection
- Eaton / Tripp Lite
- Power Distribution Units (PDUs)
- PDU Series
- Search
- Tripp Lite PDUH20DV 1.6-3.8kW Single-Phase 100-240V Basic PDU 14 Outlets (12 C13 & 2 C19) C20 with L6-20P Adapter 12 ft. (3.66 m) Cord 1U Rack-Mount
Datasheet
The Tripp Lite PDUH20DV Basic PDU provides reliable power distribution in a compact 1U horizontal form factor. Featuring an L6-20P input and supporting dual voltage (100-250V) at 20A this unit offers 12 C13 and 2 C19 outlets for connecting various devices.
Ideal for rackmount applications the PDUH20DV simplifies power management and ensures equipment receives consistent power. Its versatile design makes it suitable for diverse IT environments.
| DETAIILS | |
| Manufacturer | Tripp Lite |
| Manufacturer Part Number | PDUH20DV |
| FEATURES & SPECIFICATIONS | |
| Grounding | Grounding lug |
| OVERVIEW | |
| PDU Type | Basic |
| UPC Code | 037332158963 |
| STANDARDS & COMPLIANCE | |
| Product Certifications | IEC 62368-1; CAN/CSA-C22.2 No. 62368-1 (Canada); NOM (Mexico); UL 62368-1 |
| Product Compliance | RoHS; FCC Part 15 Class A (USA) |
| SURGE / NOISE SUPPRESSION | |
| Automatic Shut-Off | No |
| Details | |
| Category | Power Distribution Units (PDUs) |
| Environmental | |
| Operating Temperature Range | 32 to 104F (0 to 40C) |
| Relative Humidity | 5% to 95% non-condensing |
| Storage Temperature Range | -22 to 122F (-30 to 50C) |
| Operating Elevation | 0-10000 ft. (0-3000 m) |
| Input | |
| Input Connection Type | NEMA L6-20P; IEC-320 C20 |
| Input Cord Details | Input cable is detachable PDU C20 inlet |
| Input Cord Length (ft.) | 12 |
| Input Cord Length (m) | 3.66 |
| Input Phase | Single-Phase |
| Maximum Input Amps | 16 |
| Maximum Input Amps Details | Agency de-rated to 16A continuous |
| PDU Input Voltage | 100; 120; 125; 127; 200; 208; 220; 230; 240 |
| PDU Plug Type | NEMA L6-20P; IEC-320 C20 |
| Recommended Electrical Service | Single-phase 16/20A 100-240V service |
| Output | |
| Frequency Compatibility | 50 / 60 Hz |
| Output Capacity (kW) | 3.84 |
| Output Capacity Details | 3.84kW (240V) 3.68kW (230V) 3.52kW (220V) 3.33kW (208V) 3.2kW (200V) 2.03kW (127V) 1.92kW (120V) 1.6kW (100V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet |
| Output Nominal Voltage | 100-240V |
| Output Receptacles | (12) C13; (2) C19 |
| Physical | |
| Minimum Required Rack Depth (cm) | 17.27 |
| Minimum Required Rack Depth (inches) | 6.8 |
| Outlets Measurement (Center to Center) | Distance between front (C13) outlets = 28.75mm; Distance between rear (C19) outlets = 55mm; Distance between rear (C13) outlets = 28.75mm |
| PDU Form Factor | Horizontal (1U) |
| Shipping Dimensions (hwd / cm) | 5.72 x 27.69 x 51.05 |
| Shipping Dimensions (hwd / in.) | 2.25 x 10.90 x 20.10 |
| Unit Dimensions (hwd / cm) | 445 x 438 x 95 |
| Unit Dimensions (hwd / in.) | 1.750 x 17.250 x 3.750 |
| Unit Weight (kg) | 1.70 |
| Unit Weight (lbs.) | 3.75 |
| Form Factors Supported | 1U rackmount 0U vertical rackmount wall-mount and under-counter installation |
| Material Of Construction | Metal |
| Rack Height | 1U |
| Shipping Weight (kg) | 2.49 |
| Shipping Weight (lbs.) | 5.50 |
| Warranty | |
| Warranty/Returns | 30 Days |